Use this free Voltage Drop Calculator to estimate the voltage lost as electrical current travels through a wire or cable. Whether you are planning a residential electrical installation, checking cable sizes, or working on an electrical project, this tool helps you understand voltage drop and its effect on electrical performancee enter your supply voltage, current, cable length, conductor material, and wire size to calculate the estimated voltage drop. You can also use the results to understand the percentage of voltage lost and the voltage available at the load.
Enter the conductor area in mm².
This calculator uses a simplified resistance-based estimate. AC calculations do not include cable reactance, power factor, operating temperature, or installation-specific correction factors. Verify conductor sizing, ampacity, protection, and applicable electrical codes before installation. This calculator is not a substitute for professional electrical design.
Follow these steps to estimate voltage drop in an electrical cable:
Enter the supply voltage, such as 120 V or 230 V.
Enter the current flowing through the cable in amperes (A).
Enter the cable length and select the correct length unit.
Select the conductor material, such as copper or aluminum, if available.
Enter the wire size or conductor cross-sectional area.
Select the electrical system, such as DC, single-phase AC, or three-phase AC, if supported.
Click Calculate to estimate the voltage drop.
Review the voltage drop in volts, percentage, and remaining load voltage.
Make sure you enter the cable’s one-way length unless the calculator specifically asks for the total circuit length.
Depending on the calculator’s available features, the results may include:
Voltage Drop: The estimated voltage lost between the power source and the load.
Voltage Drop Percentage: The voltage loss expressed as a percentage of the supply voltage.
Receiving Voltage: The estimated voltage available at the load after voltage drop.
Cable Resistance: The electrical resistance of the conductor.
Conductor Material: The selected material, such as copper or aluminum.
Wire Size: The selected conductor size or cross-sectional area.
Circuit Type: The selected DC, single-phase, or three-phase configuration.
These results help you evaluate cable performance and understand whether a conductor may be suitable for a particular electrical installation.
Voltage drop is the reduction in electrical voltage that occurs as current travels through a wire or cable.
Every electrical conductor has some resistance. When current flows through that resistance, part of the electrical energy is converted into heat, causing the voltage measured at the load to be lower than the voltage at the source.
For example, if a power source provides 230 volts and the cable has a voltage drop of 5 volts, the approximate voltage at the load is:
230 − 5 = 225 volts
Voltage drop is a normal electrical phenomenon. However, excessive voltage drop can affect equipment performance, cause poor operation, and increase energy losses.
The amount of voltage drop depends on several factors, including cable length, current, conductor material, wire size, temperature, and circuit configuration.
Voltage drop can be calculated using the conductor’s resistance, the current flowing through it, and the circuit arrangement.
For a simple DC circuit or a single-phase resistive circuit, a commonly used approximation is:
Voltage Drop = 2 × Length × Current × Resistance per Unit Length
The factor of 2 accounts for the outgoing and return conductors in a two-wire circuit when the entered length is one-way.
For a DC two-wire circuit:
Vd = 2 × L × I × ρ ÷ A
Where:
Vd = Voltage drop in volts
L = One-way cable length in meters
I = Current in amperes
ρ = Conductor resistivity in Ω·mm²/m
A = Conductor cross-sectional area in mm²
For a single-phase AC circuit, a more complete approximation is:
Vd = 2 × L × I × (R cos φ + X sin φ)
Where:
L = One-way cable length
I = Current in amperes
R = Conductor resistance per unit length
X = Cable reactance per unit length
φ = Load power-factor angle
cos φ = Power factor
For a simple resistive load with a power factor close to 1, the reactance contribution may be small.
For a balanced three-phase AC circuit, an approximate voltage drop formula is:
Vd = √3 × L × I × (R cos φ + X sin φ)
The exact calculation depends on conductor arrangement, cable impedance, power factor, and applicable electrical standards.
To calculate voltage drop as a percentage:
Voltage Drop (%) = (Voltage Drop ÷ Supply Voltage) × 100
For example, if the voltage drop is 5 volts on a 230-volt supply:
(5 ÷ 230) × 100 = 2.17%
The approximate voltage available at the load is:
Load Voltage = Supply Voltage − Voltage Drop
For example:
230 − 5 = 225 volts
These formulas are simplified calculation models. Actual AC cable calculations may need conductor temperature, reactance, power factor, and installation-specific correction factors.
Here are practical examples showing how voltage drop changes with cable length, current, and conductor size.
The following examples use a simplified DC two-wire calculation with copper resistivity of approximately 0.01724 Ω·mm²/m at 20°C.
Electrical details:
Supply voltage: 230 V
Current: 16 A
One-way cable length: 30 m
Conductor material: Copper
Cable cross-sectional area: 2.5 mm²
Formula:
Vd = 2 × L × I × ρ ÷ A
Calculation:
Vd = 2 × 30 × 16 × 0.01724 ÷ 2.5
Vd = 6.62 V approximately
Voltage drop percentage:
(6.62 ÷ 230) × 100 = 2.88%
| Electrical Detail | Result |
|---|---|
| Supply Voltage | 230 V |
| Current | 16 A |
| Cable Length | 30 m |
| Conductor | Copper |
| Cable Size | 2.5 mm² |
| Voltage Drop | 6.62 V |
| Voltage Drop Percentage | 2.88% |
| Approximate Load Voltage | 223.38 V |
This example shows how cable resistance causes voltage to decrease between the supply and the load.
Electrical details:
Supply voltage: 230 V
Current: 10 A
One-way cable length: 50 m
Conductor material: Copper
Cable cross-sectional area: 2.5 mm²
Calculation:
Vd = 2 × 50 × 10 × 0.01724 ÷ 2.5
Vd = 6.90 V approximately
Voltage drop percentage:
(6.90 ÷ 230) × 100 = 3.00%
| Electrical Detail | Result |
|---|---|
| Supply Voltage | 230 V |
| Current | 10 A |
| Cable Length | 50 m |
| Conductor | Copper |
| Cable Size | 2.5 mm² |
| Voltage Drop | 6.90 V |
| Voltage Drop Percentage | 3.00% |
| Approximate Load Voltage | 223.10 V |
A longer cable generally produces greater voltage drop when the other conditions remain unchanged.
Electrical details:
Supply voltage: 230 V
Current: 20 A
One-way cable length: 30 m
Conductor material: Copper
Cable cross-sectional area: 4 mm²
Calculation:
Vd = 2 × 30 × 20 × 0.01724 ÷ 4
Vd = 5.17 V approximately
Voltage drop percentage:
(5.17 ÷ 230) × 100 = 2.25%
| Electrical Detail | Result |
|---|---|
| Supply Voltage | 230 V |
| Current | 20 A |
| Cable Length | 30 m |
| Conductor | Copper |
| Cable Size | 4 mm² |
| Voltage Drop | 5.17 V |
| Voltage Drop Percentage | 2.25% |
| Approximate Load Voltage | 224.83 V |
A larger conductor cross-sectional area generally reduces resistance and voltage drop.
Electrical details:
Supply voltage: 230 V
Current: 16 A
One-way cable length: 30 m
Conductor material: Aluminum
Cable cross-sectional area: 4 mm²
Using approximate aluminum resistivity of 0.0282 Ω·mm²/m at 20°C:
Vd = 2 × 30 × 16 × 0.0282 ÷ 4
Vd = 6.77 V approximately
Voltage drop percentage:
(6.77 ÷ 230) × 100 = 2.94%
| Electrical Detail | Result |
|---|---|
| Supply Voltage | 230 V |
| Current | 16 A |
| Cable Length | 30 m |
| Conductor | Aluminum |
| Cable Size | 4 mm² |
| Voltage Drop | 6.77 V |
| Voltage Drop Percentage | 2.94% |
| Approximate Load Voltage | 223.23 V |
Aluminum generally has higher electrical resistivity than copper, so a larger aluminum conductor may be needed to achieve a similar voltage drop under comparable conditions.
The following table shows illustrative voltage drop values for copper conductors in a DC two-wire circuit.
Assumptions:
Copper resistivity: 0.01724 Ω·mm²/m
One-way cable length: 10 meters
Current: 10 amperes
Conductor temperature: approximately 20°C
| Cable Size | Approximate Voltage Drop |
|---|---|
| 1.0 mm² | 3.45 V |
| 1.5 mm² | 2.30 V |
| 2.5 mm² | 1.38 V |
| 4.0 mm² | 0.86 V |
| 6.0 mm² | 0.57 V |
| 10 mm² | 0.34 V |
| 16 mm² | 0.22 V |
| 25 mm² | 0.14 V |
These are simplified resistance-based values. They are not cable ampacity ratings or installation approval values.
Several factors influence the amount of voltage lost in an electrical cable.
Longer cables have greater electrical resistance. As cable length increases, voltage drop generally increases.
Higher current produces greater voltage drop across the same conductor resistance.
Thicker conductors have a larger cross-sectional area and generally lower resistance. Using an appropriately larger conductor can reduce voltage drop.
Copper and aluminum have different electrical resistivities. Copper generally has lower resistance than aluminum for the same conductor dimensions.
Conductor resistance usually increases as conductor temperature rises. A calculation based only on 20°C resistance may underestimate the voltage drop of a warmer cable.
DC, single-phase AC, and three-phase AC circuits use different voltage drop calculations.
In AC circuits, load power factor and cable reactance can affect the voltage drop, particularly in longer cables and larger installations.
Voltage drop is important because electrical equipment is designed to operate within specified voltage ranges.
Excessive voltage drop may cause:
Lights to become dimmer.
Motors to run inefficiently or have difficulty starting.
Equipment to malfunction.
Increased electrical losses and cable heating.
Reduced performance of electrical devices.
Maintaining an appropriate voltage at the load helps electrical systems operate reliably.
Acceptable voltage drop depends on the country, electrical code, installation type, circuit purpose, and equipment requirements.
Some electrical design guidelines use approximately 3% for branch circuits and 5% for the combined feeder and branch-circuit drop as planning recommendations. These figures are not universal legal limits.
Always check the electrical code and standards applicable to your location.
For an important installation, cable selection should consider more than voltage drop. Current-carrying capacity, short-circuit withstand, protective-device coordination, insulation rating, installation method, and environmental conditions must also be evaluated.
If your calculated voltage drop is too high, consider these general design options:
Use a Larger Cable: A conductor with a larger cross-sectional area generally has lower resistance.
Reduce Cable Length: Where practical, position equipment closer to the power source.
Choose the Correct Material: Compare copper and aluminum conductor characteristics for the application.
Review the Load Current: Make sure the circuit is designed for the actual expected current.
Check Connections: Loose, damaged, or corroded connections can create additional resistance.
Review the Supply Voltage: Confirm that the source voltage is appropriate for the connected equipment.
Use Proper Electrical Design: Follow applicable standards and obtain professional verification for installations.
Never reduce cable size or change protective devices simply to achieve a lower cost without checking electrical safety requirements.
Voltage drop and power loss are related but describe different electrical quantities.
Voltage Drop: The reduction in voltage as current passes through a conductor. It is measured in volts.
Power Loss: The electrical power converted into heat because of conductor resistance. It is measured in watts.
For a simple resistive circuit:
Power Loss = Current² × Resistance
A higher current or greater resistance can increase cable power loss.
Reducing unnecessary resistance helps improve electrical efficiency and reduce heat generation.
Different electrical calculators are designed for different purposes.
Voltage Drop Calculator: Estimates voltage loss across electrical wires and cables.
Wire Size Calculator: Helps estimate conductor size based on electrical requirements.
Ohm’s Law Calculator: Calculates voltage, current, resistance, and power.
Power Calculator: Calculates electrical power using voltage and current.
Watt to Amp Calculator: Converts electrical power into current using voltage and other required details.
Electrical Cost Calculator: Estimates electricity costs based on energy usage and tariff.
Choose the appropriate calculator depending on the electrical calculation you need.
A Voltage Drop Calculator estimates how much voltage is lost as electrical current travels through a wire or cable. It uses details such as cable length, current, conductor material, wire size, and circuit type.
For a simple DC two-wire circuit: Voltage Drop = 2 × Length × Current × Resistivity ÷ Conductor Area The formula uses one-way cable length and conductor resistivity. AC circuits may require additional resistance, reactance, and power-factor terms.
Voltage drop occurs because electrical conductors have resistance. When current flows through a conductor, some voltage is lost across that resistance.
Yes. Longer cables generally have higher resistance and produce greater voltage drop when current and conductor size remain unchanged.
Yes. Larger conductors generally have lower resistance and reduce voltage drop compared with smaller conductors of the same material and length.
Copper generally has lower electrical resistivity than aluminum for the same conductor dimensions. However, aluminum can be used with appropriately selected conductor sizes and approved connections.
Voltage drop percentage expresses the voltage lost as a percentage of the source voltage. Formula: Voltage Drop (%) = (Voltage Drop ÷ Supply Voltage) × 100
The acceptable value depends on the applicable electrical code, installation, circuit type, and equipment. Some design guidelines use 3% for branch circuits and 5% for combined feeder and branch circuits, but these are not universal requirements.
Yes. Voltage drop occurs in both AC and DC circuits. However, AC calculations may also need to consider cable reactance and load power factor.
Voltage drop is the reduction in electrical voltage measured in volts. Power loss is the electrical power converted into heat in the conductor, measured in watts.
Common methods include using a larger conductor, reducing cable length, selecting an appropriate conductor material, and checking electrical connections.
Yes. Conductor resistance generally increases with temperature, which can increase voltage drop. Calculations should account for operating temperature when accuracy is important.
Yes. You can use this Voltage Drop Calculator for free without registration or a subscription.
A few of the most-used tools in each hub.
This Voltage Drop Calculator is provided for general educational and preliminary electrical planning purposes. Its results are estimates and should not be treated as approval of an electrical installation actual voltage drop depends on conductor temperature, cable construction, installation conditions, current, power factor, reactance, connections, and applicable electrical standards always verify cable ampacity, protective-device coordination, short-circuit requirements, installation method, and local electrical code requirements before selecting or installing a cable for electrical installations, consult a qualified electrician or electrical engineer.